Technical resource

Synergic MIG: what the machine is really doing, and why trim is not a heat knob

Synergic control is not the machine setting everything, it is not some magical function, it is not pulse, and it is not controlling your arc. It is a library of settings held in the machine’s memory: a relationship between amps and volts, built from three inputs, wire type, wire size and shielding gas, that somebody measured once to create a synergic line. You set the amps and you trim the volts. Trim is the quarter turn you give it when the job in front of you is not the job the curve was measured on.

Synergic decides what the machine asks for. Your hand decides what the arc gets.

Four different people misunderstand synergic welding in four different ways, and I’ve had all four conversations this year. The welder thinks the dial sets amps. The supervisor thinks trim is a heat knob. The salesperson thinks the machine sets everything, because that is what the sales brochure said. And the fab shop owner thinks the money bought a productivity gain. Every one of those came out of the way the machines are sold, the way the manuals are written, and the fact that very few people take the time to explain it properly. It matters, because this is part of competence.

So here’s the explanation, with the curve on screen so you can break it yourself. If you would rather have it on paper, the full article, a two page summary and a shop floor guide to print and post up are all at the foot of this page.

The synergic line, live

Build the curve, then break it

Pick a wire, a diameter and a gas, then set the current the way you would on the machine. The wire feed speed in brackets is what the machine commands to get there, and it is the only number it really controls. The dots are points a consumable maker actually published. Then wind the trim off nominal, run your stick-out long, or load a wire the program was never written for, and watch the amps at the arc leave the number on the dial. Nothing here stops you running a mismatched program. Neither does the machine.

The one knob. The wire feed speed in brackets is what the machine actually commands.
Offset from the stored curve. Zero is on the line.
Your hand. The machine cannot see this.
For the arc energy figure only.

Arc voltage against welding current

  • Stored synergic line
  • Trim authority, plus or minus 5 v
  • What the loaded wire wants
  • Published breakpoint
  • Where you are
Arc voltage against welding current for the selected wire, diameter and gas, with the trim band and the current operating point. The wire feed speed the machine commands is shown in brackets under each current tick.

What you dial up against what the arc gets

  • What the dial says, at nominal ctwd
  • What the arc actually gets, at your ctwd
  • Spray transition current
The current set on the dial against the current the arc actually receives. The one to one line is what the dial claims. The lower line is what the arc gets at the selected contact tip to work distance.

Transfer modedip
Wire feed speed commanded5.08m/min
Curve volts21.0v
Volts at the arc21.0v
Arc length1.5mm
Electrode extension13.5mm
Current on the dial200a
Amps at the arc200a
Off the curve by0a
Trim needed to suit the wire0.0v
ctwd sensitivity5.2a/mm
Deposition rate2.7kg/h
Arc energy0.84kj/mm
Nominal ctwd for this curve16mm
Show the numbers behind the two charts
The selected curve, sampled at even current steps across its published range. The dial amps are what you set. The arc amps are what the arc receives at the contact tip to work distance you set.
Current on the dial
a
Wire feed speed
m/min
Curve voltsVolts at the arcAmps at the arcDeposition
kg/h

Trim is shown in volts because that is what most machines sold in Australia actually use. EWM gives plus or minus 5 v direct, Kemppi 0.1 v steps, ESAB 0.25 v steps as an offset from the synergic line, Cigweld up to plus 5 v and calls it heat control, Fronius a percentage of the curve value, Lincoln a dimensionless 0.50 to 1.50 with no published conversion to volts. Read your own dial against this, do not assume the numbers transfer.

When this applies, and when it does not

This applies to any gmaw or fcaw power source with stored programs: synergic cv, synergic pulse, and the controlled short circuit processes that sit inside a synergic interface. If your machine has a wire and gas selection, a single primary knob, and a second knob called trim, arc length correction, fine tuning, arc adjust or heat control, this is your machine.

It does not apply to a plain constant voltage machine with independent volts and wire speed. On that machine you are setting the voltage yourself, and there’s no stored curve to leave. Read Volts, amps and the self-adjusting arc first if the words stick-out, arc length and self regulation are not already one thought in your head. This page is the sequel to it and assumes it.

It also does not apply to gtaw or mmaw. Those are constant current processes where the welder holds the arc length by hand. Everything below turns on the fact that in gmaw nobody does.

The machines this came from

Two Australian machines, both from the early days of synergic control, and between them they carry every idea on this page. Three inputs picked on switches. One knob for the current. One knob for the arc length. A display that tells you the program, not the arc. Worth a look before you read the rest, because nothing that follows is new.

Annotated front panel of a WIA Synchro Pulse CDT 450 remote control showing the ARC CURRENT and ARC LENGTH knobs
WIA Synchro Pulse CDT 450 remote. ARC CURRENT picks the point on the line, amps on the inner scale and pulse amps on the outer. ARC LENGTH, minus 3 to plus 3, is trim. Restored and annotated.
A WIA Synchro Pulse CDT 450 remote control box mounted on a welding machine in a workshop
The same remote, in service. These shipped with the remote as the operator interface and no knobs on the wire feeder at all. Lose the remote and you had no machine.
Digital display on a WIA CDT wire feeder reading 1.2 STAINLESS 316LSI and 5.0 metres per minute
A later CDT wire feeder. 1.2 STAINLESS 316LSI across the top with the gas under it, and 5.0 metres a minute below. The top line is the three inputs. The bottom line is the unit it is set in. Neither is a measurement of the arc.
A WIA CDT welding power source and wire feeder still in use in a workshop
A WIA CDT, still in a workshop. The gear was good in 1983 and it is better now. That was never the problem.
A CIG Transmig 350 Pulse welding machine with Synergic Control printed on the front panel
CIG Transmig 350 Pulse. Synergic Control, printed on the front, in the 1980s. What gets sold as a modern feature has been on the front of Australian machines for forty years.
Front panel of a CIG Transmig 350 Pulse showing WIRE, MATERIAL and MODE selector switches with CURRENT and FINE VOLTAGE knobs
The panel that proves the point. MATERIAL toggles mild steel, stainless or aluminium. WIRE is a four position selector, 1.2S, 1.6S, 0.9H, 1.2H. MODE toggles co2 or Ar/co2. Three inputs, three switches. The crater group carries its own CURRENT and FINE VOLTAGE, minus 5 to plus 5. Trim, under an older name.
Remote control for a CIG Transmig 350 Pulse with ARC CURRENT and ARC LENGTH knobs
CIG Transmig 350 Pulse remote. ARC CURRENT on top, pulse amps on the outer scale and amps on the inner. ARC LENGTH underneath, minus 5 to plus 5. Not heat, not power, not fine tuning. Arc length.
A well used CIG Transmig 350 Pulse in a workshop with a handwritten warning above the control panel
Process control, 1980s style. The handwritten warning above the panel is doing the job a documented setting range should be doing. The red remote sitting on top is where the two knobs that matter are.

Photographs from the author’s collection and from Australian auction listings. Two have been digitally restored so the panel markings are legible.

Same facts, same numbers, same story. The advanced version adds the equations, the clause references and the point where the story stops being true.

Where the word comes from

It’s Greek. syn means together, ergon means work. Synergia, working together.

Note what it does not mean. It isn’t “one plus one equals three”. That meaning is modern, about 1957, and the management consultants flogged it to death. The welding meaning is the old one: two things working together instead of fighting each other.

Who came up with it

Someone called Amin, writing in Metal Construction in Britain, 1981. It’s a research term, not marketing, and it’s about 45 years old.

The problem was pulsed MIG. Too many knobs for anyone to set by hand: peak current, background current, frequency, pulse width, ramp rates. So Amin made the whole lot follow one input.

Britain named it. Australia already had it running. CSIRO had a pulsed current generator working in 1979, and Welding Industries of Australia sold it here from September 1983 as the Synchro-Pulse CDT. Two knobs on the front: ARC CURRENT and ARC LENGTH. That is this whole page, in a die-cast box, forty odd years ago. The photographs above are that machine.

What it’s actually doing, and this surprises people

It isn’t controlling your arc.

All a synergic line is, is a relationship between amps and volts, worked out for three things:

  • what wire
  • what size
  • what gas

Somebody did a heap of work to find out what the volts should be for the amps, for every combination of those three. Then they wrote it down and loaded the list into your machine.

On a normal MIG you’ve got two knobs that have to agree. Wire speed sets your amps, through the burn-off. Volts sets your arc length. Only a narrow band of pairs actually works. Get it wrong one way and the wire stubs into the plate. Wrong the other way and you’ve got a long harsh arc, spatter and undercut.

Synergic just stores the pairs that work. You set one, it looks up the other.

Now the important bit. On a plain synergic machine, the thing holding your arc steady is not the computer. It’s the same physics that held it before synergic existed: when the current goes up the wire burns off faster, so the arc pulls itself back to length. That happened on a 1960s machine and it happens on yours. The synergic bit only saves you guessing the volts.

It’s a lookup table. Not a brain. Interpolation is joining the dots with a ruler: the maker measured four settings, say 100, 150, 200 and 250 amps, the machine draws a straight line between them, and every setting you pick in between comes off that line, not off anything anybody actually welded at.

Think of it as the modern version of the settings notebook that lives in a good welder’s toolbox. Somebody else’s notebook, written on somebody else’s job.

Three things to take away

  • Wrong selection is confidently wrong. Tell it co2 when you’re on an argon mix and it’ll hand you spot-on settings for a gas you haven’t got. No fault, no warning, and a bead on the plate.
  • Synergic isn’t the same as pulse. Synergic is how the machine gets set up. Pulse is how the metal crosses the arc. Plenty of welders think one means the other, and so do plenty of the people selling it.
  • It only knows three things about your job. Wire, size, gas. It does not know your stick-out and it does not know your transfer mode. Those two are where the money goes, and they’re the rest of this page.

The quarter turn

Think about a two-stroke. Chainsaw, outboard, whipper snipper, whatever you’ve got out the back.

The factory set the carburettor needles for one fuel, at one altitude, at one air temperature. At sea level on 91 it runs sweet. Take it up the hill, or change the fuel, and you give the needle a quarter turn to suit.

Nothing stops you running the factory setting anywhere you like. It just runs rich or lean. And the only thing telling you is how it sounds.

That’s a synergic machine. The stored curve is the factory setting. Trim is the quarter turn. And the arc is the sound.

Three panels showing trim wound down, left on the line, and wound up. Each panel shows a carburettor needle and a trim knob turned to the same angle, the arc length that results, and the weld section, with wire feed speed, deposition and bead size identical in all three.
The quarter turn. Trim down, on the line and trim up: the needle, the trim knob, and the same three settings in weld metal underneath. Read the bottom row of each panel. Wire feed speed, deposition and bead size are identical in all three, and nothing on the machine says otherwise. Schematic, not to scale.

Somebody in a laboratory ran that exact wire, in that exact gas, at that exact diameter, at one stick-out, and wrote down the right settings. Then they loaded the list into your machine. That list is the synergic line. Four points on a graph, usually. Straight lines in between. That’s it. It’s not clever and it isn’t watching you.

Lean and rich, in weld metal

Wind a two-stroke lean and it screams, gets hot and seizes. Wind trim down too far and the wire stubs into the plate before it melts. Harsh popping, stuttering, whiskers, and lack of fusion.

Wind it rich and it four-strokes, fouls and won’t rev. Wind trim up too far and the arc goes long and lazy, the arc root lifts off the leading edge of the pool, and you get undercut at the toes and porosity as the gas coverage lifts.

Same knob. Same two extremes. Same feedback, which is your ears. A dip transfer arc that’s right is a smooth fast crackle, like bacon. Spray is a smooth hiss. If it’s popping harshly, you’re lean.

Factory settings are right for one day, in one place, on one fuel.

So what does the primary knob do

It moves you along the list. Nothing else. On some machines that knob reads in metres per minute, on others it reads in amps, and on others it reads in millimetres of plate thickness. Same knob, three different units, and no manual tells you they’re the same knob. It’s like calling a length 25 mm, 2.5 cm or 0.025 m. One thing, three ways of saying it.

And this is the bit that costs money. When the dial says amps, you are not setting amps. You’re picking a point on the list, and the machine looks up the wire speed and the volts that go with it. The actual amps still depend on how far you’re holding the gun out, how good your earth is, and whether the tip’s shot. The machine has no idea about any of those.

So pick one unit and stay on it across the shop. Amps is the one worth standardising on, because amps is the number that turns up on every procedure sheet and every report you will ever have to defend, and it’s the one arc energy comes off. A shop where one welder dials amps, the next dials plate thickness and the third dials metres per minute has three mental models of the same machine, and not one of them lines up with the sheet. The makers were trying to simplify it. Mostly they’ve convinced people it’s three different things.

And trim

Trim is the quarter turn. Zero trim means you’re on the list, using the arc length the laboratory wrote down. Wind it up and the arc gets longer. Wind it down and it gets shorter.

Roughly a millimetre of arc per volt of trim. So plus 3 volts is about 3 mm more arc. Plus 5 is about 5 mm, and 5 mm is a lot of arc.

What trim is not is a heat knob. It doesn’t touch the wire speed, so your deposition doesn’t change and your amps barely move. Cigweld calls it Heat Control on the Transmig 355i and that name has done real damage, because someone chasing a fusion problem winds up the trim, gets a wider, flatter, prettier looking bead, and has not fixed the fusion.

It isn’t arc dynamics or inductance either, and those two get mixed up with it constantly. Different knob, different job. Trim moves the voltage, and voltage is arc length. That’s the lot.

People call volts heat for a reason, mind you. Lengthen the arc and you get more visible light, a more fluid pool and a wider bead, so it looks hotter. And the arc energy sum backs it up, amps times volts over travel speed. But most of the energy comes from the amps, and it has to: feed more wire and you need more energy to burn it off. Amps is wire feed by another name.

One knob, a different name on every machine, and none of the numbers transfer

Trim on a Lincoln. Arc length correction on a Fronius. Fine tuning on a Kemppi. Arc length on a Miller and a Migatronic. Heat Control on a Cigweld. Arc length correction in volts on an EWM. And on a Lincoln in stt mode, the same knob genuinely does change heat input, because in stt it adjusts the tail-out and the background current instead. One word, one knob, three different jobs depending on which mode is loaded. So when a welder is confused about trim, that isn’t them being thick as two short planks. That’s us not being consistent and not teaching it. They carry across what the last machine taught them.

The one that costs money: your stick-out

The list was written at one stick-out. On the 1.2 mm solid wire in co2 example in the tool above, Lincoln published it at 13 to 19 mm, so call it 16.

Now reach into a joint. Everybody does it. Your stick-out goes out to 25 mm.

The wire speed hasn’t changed. The volts on the display haven’t changed. The program hasn’t changed. Nothing on that machine has moved. And the amps at the arc have gone from about 200 down to about 174.

You’ve lost 13% of your current, and every number in front of you says you haven’t. Your deposition is identical, because deposition is just wire speed times cross section. So the bead looks the same size. It just isn’t fusing the same.

That’s cold lap on a machine that “was set right”. That’s the whole mechanism, and I see it constantly.

What to do about it

  • Learn your nominal stick-out and hold it. Roughly 10 to 12 mm on 0.8 and 0.9 mm dip transfer, 15 to 20 mm on 1.2 mm spray, out to 25 mm on 1.6 mm cored. It’s in the tool above for whatever you’ve selected.
  • Check the program matches what’s on the machine. Not the wire you meant to load. The one that’s actually in it, and the gas that’s actually in the bottle. A synergic machine will happily weld on the wrong program. It won’t fault, it won’t warn you, and it’ll still put a bead down.
  • Never run cored wire on a solid wire program. Metal cored burns off faster at the same current because the current runs in the sheath, not the core. 1.2 mm metal cored puts down 5.4 to 6.4 kg an hour against 3.6 to 4.5 for solid the same size. Run it on the solid program and you get undercut. Thats documented, not a maybe.
  • If you’re winding trim to the stops, stop and look at why. Next section.

You can run any line with any wire and any gas

Nobody tells you this part.

Nothing stops you running the wrong program. The machine will not fault. It won’t warn you. It’ll weld, and it’ll put a bead down that looks like a bead.

No 0.9 mm line in your machine? Load the 1.0 mm line, run the 0.9 wire on it, and trim the volts to suit. That’s a legitimate workaround and I wouldn’t blink at a welder doing it.

What it costs you is ‘accuracy’. The curve has stopped doing the work and you’re doing it by hand.

And the bill is smaller than you’d think one size away. Running 0.8 wire on the 0.9 program wants about half a volt of trim at 100 amps, and about 2.6 volts by 250. Go two sizes, 0.9 wire on the 1.2 program, and you need nearly 3 volts at 250 and 8 volts at 380, which is off the end of the knob.

So the rule’s simple. One size away is nearly free at the bottom of the range and gets worse as you wind it up. Two sizes away runs out of knob at the top. The gap always widens with current, which is why the borrow that ran beautifully on 3 mm plate falls apart when the same welder goes up to heavy section.

Gas is the same story, and the direction surprises people. Load a spray tuned argon program, run co2 on it, and you’ll be winding trim down, several volts, and you still won’t get spray, because co2 can’t produce it at any current. Lincoln’s own SuperArc L-56 sheet has 1.2 mm in straight co2 at 19 to 21 volts and 145 to 200 amps, short circuit, and the same wire in 90 argon 10 co2 at 27 to 30 volts and 285 to 340 amps, spray. Same wire, same page, and co2 sits right down the bottom. Going the other way you wind up. Know which way you’re borrowing and by how much.

Then write the trim value on the sheet. That’s the whole discipline. A borrowed program with the trim written down is a controlled process. A borrowed program with the trim left to whoever picks up the gun is not.

Trim at the stops is telling you something

If a welder consistently needs a lot more volts than the list says, the list isn’t wrong. One of three things is, and all three are ten minute checks:

  1. The stick-out is long. The extra resistance has dropped the current, so the list’s volts are now too low for the arc that’s actually there.
  2. The program doesn’t match the wire or the gas actually loaded. Change the gas and a trim of zero is a completely different voltage.
  3. Volts are getting lost between the machine and the arc. Four volts down long leads and dodgy connections on a 31 volt arc is documented. The machine sends what it was asked for. The arc never gets it. So the trim goes up to make up the difference.

Gun angle is the fourth, and it’s the one that beats the feedback loop entirely.

So log the trim next to the current on every machine in the shop. A fleet sitting near nominal has the right programs, has been set up properly, and has welders holding their stick-out. Anything on the stops, or past about plus or minus 3 volts, is telling you which of those three you’ve got. Costs nothing but a bit of time, and it’s the closest thing to a free diagnostic the equipment offers.

What it sounds like

  • Trim too low, arc too short. Harsh popping. Stubbing. The wire drives into the plate before it melts and you can feel the feed motor labouring. Whiskers. Burnback to the tip if you keep going.
  • Trim too high, arc too long. Lazy, wandering, wide. Spatter comes back. Undercut at the toes. And porosity, because the arc root is sitting up high and the gas column isn’t wrapping it any more.
  • Right. Dip transfer is a smooth fast crackle, like bacon. Spray is a smooth hiss. If it’s popping harshly it’s either the trim or the wire speed, and the fix is not always trim.

And the gas, which the machine cannot see at all

No synergic machine senses gas. Not what’s in the bottle, not the flow, not a leak. And composition is the big one, because there’s no such thing as one argon co2 mix. Some shops run 80 argon 20 co2, some run 82/18, and then there are the tri mixes, argon with 16 per cent co2 and 3 per cent oxygen. Under ISO 14175 the first two are both M21, which covers anything from 15 to 25 per cent co2. The tri mix is M26, and your machine may not carry a program for it at all.

Then look inside the designation. Any component above 5 per cent can be delivered within plus or minus 10 per cent of its nominal value. Not ten percentage points, ten per cent of the number. So a nominal 20 arrives anywhere between 18 and 22, a nominal 18 arrives between 16.2 and 19.8, and both are fully compliant. That’s nearly six percentage points of co2 across two gases the machine holds one program for, and it has no way of knowing which bottle it’s being fed from. Enough to change how the arc sounds. Enough to want a volt of trim.

Straight co2 earns its own warning. Argon is a single atom and ionises into a smooth stable column. co2 has to be torn apart in the arc before it will conduct at all, and it can’t produce spray at any current. Wind the volts up on co2 expecting a nicer arc and you don’t get one. You get globular: big droplets, severe spatter, runs like a pig. A co2 procedure runs low volts on purpose. And running straight co2 in a modern shop is false economy, particularly with skills where they are, because you’re handing the welder a harder process and an erratic arc, and losing it again in spatter, to save a few dollars on gas.

Flow is the other one the machine can’t see. Turning the gas up to fix porosity can cause porosity: past roughly 21 L/min through a 16 mm nozzle the exit velocity creates a vacuum at the nozzle lip and pulls atmosphere into the plume. The working range is about 12 to 14 L/min on that nozzle. Not 28.

And the wire, which it can’t see either

Two spools can both say ER70S-6 and still run differently, because the standard allows a range, not a number. AWS A5.18 lets manganese sit anywhere from 1.40 to 1.85 per cent and silicon from 0.80 to 1.15. Those two are the deoxidisers, and they set how the pool wets, how the arc forms and how much silicate island you’re left picking off the top. A wire at the bottom of both bands and a wire at the top are both compliant ER70S-6, and they don’t run the same. Add the diameter tolerance, and copper coating on some and none on others, and it’s enough to sit you off the line.

Two reasons that matters more than it sounds. Silicon raises resistivity, and resistivity is what heats the stick-out, so two compliant wires don’t burn off at the same rate at the same current. And the wire isn’t only the thing being melted: iron vapour ionises at 7.9 electron volts against argon’s 15.76, so metal coming off the wire is a large part of what carries the current in the arc column. Change the chemistry and you’ve changed the conducting medium, not just the filler.

None of that is on the panel and none of it is in the program. It comes out as a wire that wants a different trim to the last one, on the same job.

Fault to cause, cheapest check first

Two principles before the table, because they save more time than the table does.

Principle 1, revert to manual cv to isolate the fault

Every machine here has a manual mode. ESAB has a clean toggle, Synergy off or on, on the same voltage knob. Miller’s Multimatic 255 manual has the clearest single sentence any maker offers: the left knob “adjust[s] voltage in MIG mode, arc length in Pulsed MIG mode”. If the arc is stable in manual cv at equivalent volts and wire feed speed but unstable in synergic, the fault is the program or the sensing. If it’s unstable in both, the fault is mechanical or electrical. It’s the most useful test available to a supervisor and it costs nothing.

Principle 2, trim position is data

Log it next to the current, and the wire feed speed where the machine shows it, on every machine in the shop. A fleet sitting near nominal has correct programs and welders holding their stick-out. A fleet on the stops, or habitually past about plus or minus 3 volts, is telling you the programs don’t match the consumables, or the welders don’t hold ctwd, or the circuit is losing volts. Which of the three is a ten minute check.

SymptomMost likelyThen checkThen check
Wire stubbing into the plate, feed motor labouringTrim or voltage too low for the wire feed speedWrong program: diameter set larger than the wire actually loadedDrive roll tension, liner obstruction
Stuttering and popping at arc strike, “machine gunning”Excessive standoff at the strike, loose grip on the gunVoltage too low for the wire feed speed, raise 1 v at a timeSpool brake too tight, wire slowing before ignition
Harsh, narrow, digging arcTrim or arc length too lowArc control or inductance set too tightConfirm the program before touching either
Arc long, lazy, wanderingTrim or arc length too highWrong gas or wrong program, an equal ranking documented causectwd too long, then arc blow
Welder habitually at maximum trimctwd habitually too longProgram does not match the consumable or the gasVolts lost in leads, connections, work return
Welder habitually at minimum trimProgram is for a larger diameter or a more co2 rich gas than in usectwd too short, nozzle spatter loadingGun angle beyond the feedback compensation range
Amps read low at the correct wire feed speedctwd too long: 10 mm out to 25 mm took 200 a down to 150 to 160 a in a measured testWorn or keyholed contact tipPoor work return, connections warm to the touch
Amps read high at the correct wire feed speedctwd too shortWrong wire diameter actually loadedMeter error, plus or minus 10% of range is normal
Excess spatter in pulseWrong gas for the programWrong wire diameter selectedWorn tip, inconsistent wire delivery, low inductance
Excess spatter in dipTrim or voltage too low for the wire feed speedInductance too lowco2 rich gas on an argon program
Burnback at the contact tipWire feed slowing before arc ignitionLiner, drive rolls, spool brake tensionContact tip bore keyholed
Porosity, generalGas flow too high: over about 21 L/min through a 16 mm nozzle aspirates airExcessive wire extension, limit to about 13 mm past the nozzleNozzle spatter build-up, gas leak in gun or hose, draught
Porosity at weld starts onlyStart of weld surge flow, measured over 100 L/min on a standard hosePurge time and hose volumeContamination at the start point
Undercut at the toesTrim or arc length too high, arc too wideMetal cored wire on solid wire parametersTravel speed too fast, gun angle, arc blow
Cold lap and lack of fusion with settings that look rightctwd long, current down 20 to 25% at unchanged wire feed speedArc riding the puddle instead of the leading edge, gun angle outside 0 to 15 degreesTrim too low, base metal contamination
Lack of sidewall fusion in a narrow gapArc blow deflecting the arc off the sidewallWork return position and symmetryArc length too long, a longer arc is easier to deflect
Burn-throughProgram selected by nominal thickness with no allowance for fit-upTrim or voltage too high, wire feed speed too highTravel speed too slow, heat build-up late in the run
Heat input from the display fails the wps limitAveraging error: about 23% on pulsed, 8% the other way on dipMeter tolerance, plus or minus 10% of rangeSense point at the terminals not the arc: 4 v on a 31 v arc is 13%
Connections warm to the touch after a runAdded circuit resistance degrading the pulse feedbackWork clamp condition and contact areaLead condition, connector torque
Machine “welds rough” and no parameter fault can be foundWire feed instability partly masked by the arc regulatorLiner, drive rolls, spool brake, tipCompare in manual cv to isolate the program from the circuit

That last row deserves a note, because it’s a synergic specific trap that I’ve not seen written down anywhere. On a plain cv machine a welder feels a feed problem immediately as an unstable arc and diagnoses it. On a synergic pulser the controller is actively regulating to hold the arc length and will partly compensate, so the felt feedback is attenuated. What comes back isn’t “the wire’s feeding badly”, it’s “this machine welds rough” or “the program’s no good”. The fault gets blamed on the program and the liner never gets looked at.

What to do with this

The welder

Read the manual, photograph the settings, then go and turn every knob on the machine and listen to what changes. Just make sure you can get back to where you started. There’s no better way to learn a machine than to run it out to its limits deliberately. The primary knob, whether it reads amps, wire feed speed or plate thickness, picks a point on the curve. Trim is the quarter turn. And your stick-out is the one thing on the procedure sheet you can control without a meter, so control it.

The supervisor

Record the trim next to the current across the fleet. Check the program against what is physically loaded before you check anything else, and use manual cv as the isolation test. Know the machines better than anyone on the floor: what every function does, and whether the wire feeder is displaying an honest number. If it isn’t, put an offset sticker on it so the welders know how far out it is. You are the one responsible for welding control. If you can’t dial a machine in to run properly, you are not controlling the process.

Anyone writing procedures

Record amps and volts measured with a good tong tester at the right sensing point, verify the travel speed, state the stick-out, and document the mode of metal transfer in words. List the shielding gas by ISO 14175 designation and trade name, the consumable by trade name, the power source make and model, and the program identifier where the machine has one. AS/NZS 1554.1 names synergic control once, in a note to clause 1.1, and that note adds to the confusion rather than resolving it: a procedure that records only machine settings has its range of application limited to equipment of that type, and it will not let anyone replicate what happened at the arc.

The owner

Buy synergic at changeover time, understand what you’re buying, and resource the setup with someone who knows the pitfalls. Get educated on what good looks like so you can hold consistency across a variable crew. Make sure your key people know the machines, the equipment is set up properly and the welders are trained on the interface. Don’t buy it expecting it to fix fusion, access or fit-up, because those are the three things that drive your repair rate and none of them are in the curve.

The curve is a promise made in perfect conditions. Understanding what causes the variation, and what makes the displayed values inaccurate, is what lets you repeat the weld.

Standards and editions, exactly as cited

Standard and editionClause used hereFor
AS/NZS 1554.1:2014, ninth edition, incorporating Amd 1:2015 and Amd 21.1 Note 2; 4.11 and Tables 4.11(A) to (C); 4.6.1The only place synergic control is named in the standard; requalification limits; arc energy caps of 5 kj/mm for L0 and 2.5 kj/mm for the L15 to L50 and Y grades 4.11 item letters verified against the 2000 edition only
AS 3992:20201.1.2; 5.1(c); 5.3 and Table 5.1 item 7Waveform controlled arc drafted as a peer of spray and globular; the explicit statement that the arc energy equation applies to non waveform controlled welding only
ISO 15614-1:2017 + Amd 1:20198.4.6; 8.4.7; 8.5.2.3.1 to 8.5.2.3.4Transfer mode coverage; heat input and arc energy limits; the three tier waveform scheme and the level 2 preface
ISO 15609-1:20194.4.9; 4.4.10; 4.4.16; 4.4.17What a wps must record, and the range of application consequence
ISO 9606-1:20125.1; 5.2Machine mode is not a welder essential variable; dip qualifies the other modes and not the reverse
ASME BPVC Section IXQW-409.1; QW-409.2; form QW-484ATransfer mode boundary; the three permitted heat input methods including bead size All ASME wording here is paraphrase; Section IX is paywalled and no verbatim copy was sighted
ISO/TR 18491:20266; 7.2 and Table 2; 7.4Arc energy definitions and the three methods; the sensing point for process 13(x); the meter naming test. The 2026 edition, published 23 June 2026, replaced ISO/TR 18491:2015 The 70% worst case for method A and the ten times sampling rule are transcribed from the 2015 edition. Re-check both against the 2026 text before citing them in a procedure
IEC 60974-14:2018 + Cor 1:20223.6 to 3.10; 6; Annex C.4Calibration against validation against consistency testing; standard and precision grade; Annex C.4 is titled “Pulsed MIG and synergic controls” Table 1 and Table 2 cell values and Annex C.4 not obtained
EN 50504:20084 and Table 1; 6The plus or minus 10% of true value figure, verified; yearly validation with a three month initial recheck
IEC 60974-1:2021, sixth edition16.3Located but not obtained No figure from 16.3 is quoted anywhere on this page
ISO 4063:20235.2Process 135 and 138. Note there are no ISO 4063 designations 135-P or 136-P; those are aws style suffixes
Weld Australia TGN-SG06, 20196.8; 6.15; 6.16Guidance, not normative. Conventional meters are “highly erroneous” on waveform machines and wire feed speed should be specified

Verified, derived, and modelling choice

Most pages in this industry don’t separate these three. This one does, so you can argue with it.

Verified, transcribed from a named published document

  • Every wire feed speed, voltage and current breakpoint in the appendix below, with its source named per row.
  • Nominal contact tip to work distance where the source states it. voestalpine Bohler states 15 mm for the 1.2 mm metal cored table. Hobart FabCOR states 13, 19, 25 and 25 mm graded by diameter, which is direct evidence that the curve and the nominal stick-out are a matched pair. Select-Arc states it per row. ESAB’s OK Autrod 12.51 does not, so 15 mm is used, which is the extension the burn-off coefficients were fitted at.
  • Spray transition current, 90Ar/10CO2 and 98Ar/2O2 only: 0.9 mm 175 to 185 a, 1.2 mm 215 to 225 a, 1.6 mm 280 to 290 a in 90/10, and 1.2 mm 205 to 215 a in 98Ar/2O2. Lincoln C4.200, cross-checked against ewi.
  • Contact tip to work distance sensitivity, measured independently by two organisations: Miller, gmaw spray, 15.9 to 25.4 mm took 282 a down to 213 a, which is 7.3 a per mm. ewi, gmaw-p at 5.1 m/min wire feed speed, 19.1 to 28.6 mm took 300 a down to 225 a, which is 7.9 a per mm.
  • Deposition rate from wire feed speed. Purely geometric: cross section times feed speed times density. There is no physics uncertainty in it at all.
  • The pulsed arc energy error. Norrish 2017 table 3, measured at 5 khz: spray transfer zero error, conventional dip minus 8.3%, waveform controlled dip minus 4.7%, pulsed transfer plus 23%, and the 46% error in calculated t8/5 that followed from the 8.3%.
  • The transfer mode labels on the 1.2 mm metal cored curve. Bohler labels its own rows short arc, globular and spray, so the tool uses those rather than a modelled transition.
  • Every clause quotation and clause reference, except those carrying a verify marker.

Derived from published data, with the arithmetic shown

  • Deposition factor for cored wires. ESAB’s own OK E71T-1 sheet publishes both wire feed speed and deposition rate, so the factor falls straight out. At 20.7 m/min on 1.2 mm the geometric figure is 11.03 kg/h against 7.5 published, and at 5.8 m/min it’s 3.09 against 2.1. Both give 0.68. The same method on Hobart FabCOR gives 0.90 for metal cored. Those two numbers are what the tool uses, and they are the maker’s own data solved for the unknown, not a guess.
  • The stainless joule coefficient. Select-Arc publishes 220 a at 8.3 m/min for 1.2 mm ER308LSi. Solving the burn-off equation for the joule coefficient at that point gives 1.09e-4 against 5.9e-5 for carbon steel, a ratio of 1.84. That’s why stainless runs about a fifth more sensitive to stick-out than carbon steel at the same current, and it’s consistent with stainless having several times the electrical resistivity. Checked at the far end of the same table the model runs 9% low, which is as good as this class of model gets.
  • Contact tip to work distance sensitivity. Differentiating the burn-off equation at constant wire feed speed, as set out in the advanced method above. Predicts 6.6 a per mm at 300 a from Richardson’s published coefficients with no fitting, against 7.3 and 7.9 a per mm measured. Within about 10%.
  • Validation of the worked example. Solving the burn-off equation at Lincoln’s own nominal extension for the 1.2 mm co2 operating point gives 204 a against the 200 a Lincoln published. 2% out.

Modelling choice, and where it could be wrong

  • Burn-off coefficients. Richardson, Bucknall and Stares 1994, Welding Journal Research Supplement 73(2):32s to 37s, fitted at 15 mm on mild steel. Used as published for 0.8, 1.0 and 1.2 mm. The 0.9 mm pair is interpolated. The 1.6 mm pair is extrapolated on the inverse fourth power of diameter, and the resulting arc coefficient lands on Fujimura et al. 1987’s independent figure, which is corroboration rather than proof. These coefficients set only the sensitivity, never the curve itself, so the published breakpoints stay exact at nominal stick-out and only the correction away from nominal carries the model.
  • Sheath conduction factor for cored wires, 2.5 for metal cored and 3.0 for rutile flux cored. Current flows in the metal sheath, not the core, so the conducting area is an annulus and the joule coefficient is larger than the nominal diameter implies. The direction is certain and the mechanism is documented in the burn-off literature. The two numbers are not published anywhere and I have not measured them, so treat cored wire sensitivity as indicative.
  • Arc column gradient, 1.0 to 1.6 v per mm by gas, higher for co2 on the grounds that co2’s higher thermal conductivity demands more voltage to hold a stable arc. The defensible published band is roughly 0.5 to 2 v per mm depending on gas, with one measured figure of 0.41 v per mm for aluminium in argon. This sets how far the arc moves per volt of trim, so the arc length readout is indicative rather than a measurement.
  • Nominal arc length, 1.5 mm dip, 4 mm globular, 5 mm spray, against a published free flight range of 3 to 10 mm and a dip average near zero to 2 mm.
  • Spray transition currents for M21, M12 and the 0.8, 1.0, 1.3 and 1.4 mm diameters, scaled or interpolated from the verified 90/10 and 98Ar/2O2 figures. M21 is taken as 1.05 times the 90/10 figure. Indicative only, and the tool says so on screen.
  • Clamping outside the published range. The tool clamps. No manual read for this work states what a real machine does. Clamping is the likely behaviour.
  • The claim that trim in a pulsed synergic machine acts on the background current. Documented explicitly by Kemppi. Fronius confirms the waveform is acted on without naming the parameter, and Lincoln says trim adjusts arc length without naming the actuator. The physics is sound and one maker documents it, so “usually” is an inference across the industry, not a verified generalisation.
  • The three causes behind trim at the stops. All three are documented conditions. The inference that a habitually extreme trim setting diagnoses which one you have is mine. I have not found it stated anywhere in the literature, and it is the single most useful thing on this page, so it should be the first thing anyone tries to knock down.

The published data every curve here is built on

Read the basis column. Where it says published rows, every dot on the chart above is a real published row. Where it says envelope ends only, the maker publishes the two ends of its operating range and the line between them is a straight interpolation. That distinction is the honest limit of the tool and it’s shown on screen for whatever combination you have selected.

Carbon steel solid wire

AWS A5.18 ER70S-6, ISO 14341-A G 42 3 M21 3Si1

Dia
mm
GasWire feed speed
m/min
Arc voltsAmpsNominal ctwd
mm
Basis
0.8C13.2018.06011Envelope ends onlyESAB OK Autrod 12.51 PDS
13.0024.0200
0.8M203.2018.06011Envelope ends onlyESAB OK Autrod 12.51 PDS
13.0024.0200
0.8M213.2018.06011Envelope ends onlyESAB OK Autrod 12.51 PDS
13.0024.0200
0.9C12.5418.08011Published rowsLincoln SuperArc L-56 operating procedures, 3 rows, plus the ESAB 12.51 envelope maximum
3.8119.0120
6.3522.0175
12.0026.0250
0.9M203.0018.07016Published rowsLincoln SuperArc L-56, 90Ar/10CO2 spray, 3 rows, plus the ESAB 12.51 envelope minimum
9.5323.0195
12.7029.0230
15.2430.0275
0.9M213.0018.07013Envelope ends onlyESAB OK Autrod 12.51 PDS, cross-checked Cigweld Autocraft LW1-6 PDS
12.0026.0250
1.0C12.7018.08015Envelope ends onlyESAB OK Autrod 12.51 PDS
15.0032.0300
1.0M202.7018.08015Envelope ends onlyESAB OK Autrod 12.51 PDS
15.0032.0300
1.0M212.7018.08015Envelope ends onlyESAB OK Autrod 12.51 PDS, cross-checked Cigweld Autocraft LW1-6 PDS
15.0032.0300
1.2C13.1819.014516Published rowsLincoln SuperArc L-56, 100% CO2, 3 rows, plus the ESAB 12.51 envelope maximum
3.8120.0165
5.0821.0200
15.0034.0380
1.2M132.5018.012015Envelope ends onlyESAB OK Autrod 12.51 PDS
15.0034.0380
1.2M202.5018.012016Published rowsLincoln SuperArc L-56, 90Ar/10CO2 spray, 3 rows, plus the ESAB 12.51 envelope minimum
8.8927.0285
12.0730.0335
12.7030.0340
1.2M212.5018.012015Envelope ends onlyESAB OK Autrod 12.51 PDS, cross-checked Cigweld Autocraft LW1-6 PDS
15.0034.0380
1.6C12.3028.022519Envelope ends onlyESAB OK Autrod 12.51 PDS
12.0038.0550
1.6M205.3327.032519Published rowsLincoln SuperArc L-56, 1/16 in, 90Ar/10CO2 spray
7.3729.0430
1.6M212.3028.022519Envelope ends onlyESAB OK Autrod 12.51 PDS, cross-checked Cigweld Autocraft LW1-6 PDS
12.0038.0550

Metal cored wire

AWS A5.18 E70C-6M, ISO 17632-A T 42 3 M M 1 H5

Dia
mm
GasWire feed speed
m/min
Arc voltsAmpsNominal ctwd
mm
Basis
0.9M2012.4025.020013Envelope ends onlyHobart FabCOR 86R data sheet
19.8029.0300
1.2M206.1024.020019Envelope ends onlyHobart FabCOR 86R data sheet
18.4033.0400
1.2M211.5014.08515Published rowsvoestalpine Bohler Welding, 1.2 mm metal cored welding parameters, 11 rows, DC+, 15 mm stick-out, M21
2.0014.5105
2.5016.3125
3.0018.0137
5.0021.0185
6.0022.5225
7.0024.5245
8.0027.0255
10.0028.5285
11.0029.5310
12.0030.5335
1.4M204.8024.020025Envelope ends onlyHobart FabCOR 86R data sheet
13.7032.0400
1.6M204.1024.025025Envelope ends onlyHobart FabCOR 86R data sheet
12.7032.0500

Gas shielded flux cored, rutile

AWS A5.20 E71T-1, ISO 17632-A T 42 2 P M 1 H10

Dia
mm
GasWire feed speed
m/min
Arc voltsAmpsNominal ctwd
mm
Basis
1.0M214.5022.010015Envelope ends onlyESAB OK E71T-1 product data
23.0035.0300
1.2M215.8023.015018Envelope ends onlyESAB OK E71T-1 product data
20.7035.0350
1.4M213.3022.015020Envelope ends onlyESAB OK E71T-1 product data
11.6034.0350

Austenitic stainless solid wire

AWS A5.9 ER308LSi, ISO 14343-A G 19 9 L Si

Dia
mm
GasWire feed speed
m/min
Arc voltsAmpsNominal ctwd
mm
Basis
0.9M1311.4021.017014Published rowsSelect-Arc Select 308LSi recommended welding parameters, 4 rows, 98Ar/2O2, flat and horizontal
13.1023.0185
14.2024.0200
16.6026.0205
1.0M139.9021.019514Published rowsSelect-Arc Select 308LSi recommended welding parameters, 4 rows, 98Ar/2O2
11.3023.0210
12.4024.0225
14.6026.0240
1.2M138.3021.022016Published rowsSelect-Arc Select 308LSi recommended welding parameters, 4 rows, 98Ar/2O2
9.5023.0235
10.7024.0250
12.7026.0270
1.3M137.1021.024017Published rowsSelect-Arc Select 308LSi recommended welding parameters, 4 rows, 98Ar/2O2
8.5023.0270
9.5024.0295
11.2026.0310
1.6M135.7021.026520Published rowsSelect-Arc Select 308LSi recommended welding parameters, 4 rows, 98Ar/2O2
7.6023.0305
8.4024.0335
9.5026.0350

What this page does not do

This qualifies nothing

The tool above is not a welding procedure specification, not a procedure qualification record, and no substitute for either. It’s a teaching tool built on published consumable data and a well documented melting rate model. It does not know your joint, your position, your material grade, your fit-up or your acceptance criteria.

Do not calculate arc energy for a pulsed procedure from a machine’s displayed averages. Do not assume a curve from one maker’s machine transfers to another’s. And if you’re qualifying to ISO 15614-1 level 2 on a waveform controlled machine, understand before you start that you are locking the procedure to that manufacturer and that waveform mode, and that changing either requires a new test.

Limitations, stated plainly

  • No manufacturer’s actual synergic line appears here. Almost nobody publishes them. Every curve is built from a consumable maker’s published parameter table, which carries the same information and in the stainless case carries it in the same form, four breakpoints per diameter.
  • Aluminium is deliberately absent. ESAB publishes current and voltage ranges for OK Autrod 5356 but no wire feed speed, and I couldn’t find a wire feed speed table for any aluminium mig wire to the standard of the four wires here. Modelling it and calling it data would be worse than leaving it out.
  • Curve counts are a purchasing question, not a specification. ESAB’s Aristo 500ix with the U82 Plus panel carries up to 259 manual synergic lines plus 68 robotic, with extra packages loaded by a service engineer. Kemppi and Fronius distribute curves as licensed software work packs, so the count is a commercial variable. Ask for the weld set reference list for the exact machine and firmware, not the brochure.
  • Behaviour outside the published range is undocumented. No manual read for this work states what a machine does when the commanded wire feed speed falls past the last table entry. Clamping is the likely behaviour and it’s what the tool does. The adjacent evidence is that curves must be monotonic and that non-linear scaling exists specifically to stop extrapolation violating the physics.
  • The Australian training gap is real. There is no published Australian teaching resource that explains the mechanism. Weld Australia’s resources hub is member gated and no synergic content could be confirmed beyond two paragraphs in TGN-SG06. WIA’s Weldmatic 350 product page doesn’t mention synergic at all. The most read Australian explainer, from Weldclass, explicitly declines to explain it and collapses volts and wire speed into one term it calls “current”. Meanwhile Norrish, based at Wollongong, published the field’s most rigorous definition in 2017. That’s the gap this page is written into, and if you find an error in it I’d rather hear about it than have it stand.

Take it with you

All free, no sign up, no email address. Print them, hand them out, put them on the wall.

  • PDF · 13 pages The full technical article Synergic Is Not Automatic. Four figures, one comparison table, twenty four sourced footnotes, and every number on this page traced back to a named document.
  • PDF · 2 pages The two page summary A four minute read. What synergic is, what trim really does, the four things the curve cannot see, and what it costs. Good for a toolbox talk or a management meeting.
  • PDF · poster The shop floor guide, A3 One sheet for the wall. What the machine is doing, what trim means, what it cannot see, and a six step check before you strike an arc. Same sheet in A2 and A4.

Graham Fry, Principal Welding Engineer, Technoweld Pty Ltd. Thirty years across pressure equipment, structural fabrication and welding training, in Australia and internationally. Working daily to AS/NZS 1554, AS/NZS 5131, AS 3992, AS 4041, AS 1210, ISO 3834, ISO 15614, ISO 9606 and ASME BPVC.

Disclosure: Technoweld sells welding engineering, procedure development, and welding supervision and inspection training. This page names consumable makers and equipment makers because their published documents are the evidence, not because Technoweld represents any of them. Nobody paid for a mention and nobody was given a preview.

Version 1.6, 6 September 2026. Next review September 2027. Published data appendix current at the date of transcription.